Compatibility List
The following network, hardware, firmware, Integration Drivers, and FLN applications are compatible for integration with Desigo CC.
APOGEE Networks Supported
Network | Supported | Additional Requirements |
P2 RS-485 | Y | RS-485 networks can be connected using AEM; however, direct connection is not supported. |
P2 AEM | Y | Requires one of the following: Physical AEM device Virtual AEM in a PXC |
P2 Ethernet | Y | Supported as is. |
P2 Dial-Up | X | Not supported. Must be converted to Ethernet network or AEM. |
BACnet IP | Y | Supported as is. |
ALS3 | X | Not supported. |
Hardware Supported
Hardware | Type | |
ALN | MBC Power Open Processor (562-001,002,040) | |
MBC Open Processor | ||
MEC Power Controller (549-600 series) | ||
MEC Controller | ||
PXC Compact | ||
PXC Modular | ||
Hardware | Type | |
FLN P1 | P1DXR | |
TEC | ||
LAB Controllers | ||
Point Expansion Modules | ||
PXC Compact on P1 | ||
P1 BIM | ||
Digital Energy Monitor | ||
P1 Drivers | ||
VFD | ||
Hardware | Type | |
FLN BACnet | DXR (APOGEE Firmware Revision 3.4 and later) | |
PTEC | ||
PXC UEC | ||
PPM | ||
Firmware Supported
The following list shows hardware and drivers compatible with minimal Desigo CC firmware support.
We recommended that you install\flash to the latest firmware available to ensure the best system performance and to install the most recent bug fixes.
Hardware | 2.x P2 RS-485 | 2.x P2 Ethernet | 3.x BACnet |
PXC/PXC-M | 2.8.10 and later | 2.8.10 and later | 3.2.4 and later |
PXC/PXC-M Integration Drivers | 2.8.2 or 2.8.5 | 2.8.2 or 2.8.5 | 3.1 Ver. 2 to (Select 3.5.7) |
Power Open Processor | 2.8.10 and later | 2.8.10 and later | Limited Support* |
Power Open Processor Drivers | 2.7 | 2.7 | Limited Support* |
Pre Power OP | 2.8 | N/A | N/A |
Pre Power OP Drivers | Not Supported | N/A | N/A |
Power MEC (V3) | 2.8.10 and later | 2.8.10 and later | Limited Support* |
Power MEC (V3) Drivers | 2.7 | 2.7 | Limited Support* |
Pre Power MEC (68302) | 2.8.10 and later | N/A | N/A |
Pre Power MEC Drivers | Not Supported | N/A | N/A |
SCU v5 | Not Supported | N/A | N/A |
FLNC | 2.8 | 2.7 | N/A |
* will look like a third–party BACnet device. | |||
FLN Drivers Supported
The following list shows Integration Drivers compatible with BACnet firmware (APOGEE Firmware Revision 3.2.4 and later):
- BACnet MS/TP
- Johnson Controls N2 Master
- Modbus 250/500/1000
- Siemens Firefinder XLS
FLN Application Support
Applications listed in the FLN Application Library are fully supported with pre-defined Functions and Template Graphics. While applications not found in the list are discovered and imported, you must manually create and assign Functions and Template Graphics. In this case, contact Technical Support for help.